Don't Deny the D: Taming Derivative Tuning for PID Control Of the three letters in PID, the "D" is probably the most misunderstood and certainly the least used! It is well-known that D (derivative) control is largely unnecessary for fast loops (such as flows and pressures) due to those loops' naturally quick response time. However, derivative control is extremely useful for particularly slow loops and is an absolute must-have for integrating processes such as level and insulated temperature loops. Why is D so important for these loops? The answer is in the predictive action D provides. When you drive a car and approach a stop sign, you need to apply the brake. But how much brake should you apply? Among other things, the answer depends on how fast you are going and how close you are to the stop sign. The closer you are and the faster you are going, the more brake you need in order to reach the stop sign safely. Applying too much brake or applying it too early means you will not reach the stop sign. Applying too little brake or applying it late means you will travel past the stop sign. It's the same in process control. Derivative action is a predictive brake for the controller. We want to use the right amount of D (the brake) so that we get to setpoint quickly (the stop sign) without overshooting (traveling past the goal) or undershooting (stopping short of the goal). And as anyone performing loop tuning can testify, getting the right amount of D is often a difficult task. To help understand derivative controller action, let's examine two common misuses of the D term. To aid our study, we'll examine the effects of the D term on a 3rd order integrating process with a gain rate of 0.34, a deadtime of 40 seconds, a lag time of approximately 90 seconds, and some higher order dynamics as well. In the following examples, the PID controller uses a noninteracting equation when performing its calculations. Note: Given the integrating nature of this process, PID control in these examples was used with an extremely weak integral term. This essentially created a PD-only tuning situation since the integrating (I) action is naturally built into the process dynamics. MISUSE #1: Derivative Action Too Strong: Figure 1 shows the reaction of our process to a PID controller with different D tuning settings. The orange trend uses a D term that is too strong, while the blue trend (superimposed) uses a proper D setting for this process. The P and I terms are exactly the same for both controllers.
As the trend indicates, so much braking force is applied to the process that our derivative action actually hinders the PV from reaching setpoint. Not only that, but because the derivative action is so aggressive, it is preemptively acting on what it predicts will soon be a negative SP-PV error (though the actual error remains positive). This preemptive action on a predicted negative error is what causes the saw-tooth pattern in the PV and the CO (not shown). MISUSE #2: Derivative Action Too Weak: Figure 2 also shows the reaction of our process to two PID controllers with different tuning settings. The red trend uses a D term that is too weak, while the blue trend (superimposed again) uses a proper D setting for this process (same settings as in Figure 1). The P and I terms are exactly the same for both controllers.
As the trend indicates, so little brake is applied to the process that our PV far overshoots its goal. For this process, product quality is significantly affected due to poor derivative tuning, and this particular company spends far more on natural gas to heat this loop in startup than is necessary. Multiplied out over similar loops in the rest of the plant, this is a significant energy and product resource waste—all from a poor use of derivative action in PID control. Professional Tuning, Anyone? In an ideal world, we could easily estimate the right amount of derivative action for a process. Of course, we don't live in an ideal world and trying to understand the proper amount of D to use can be a long and complicated trial-and-error process, especially if you are tuning slower temperature and level loops. What if you could have a PID loop professional monitor your process 24 hours a day, 7 days a week and continuously make recommendations about how to adjust your P, I, and D for increasingly better control? ControlSoft's Advisory Adapt Tune technology, available in the INTUNE v5 software line, provides that exact service. In a recent test, the INTUNE v5 Adapt Tune function was allowed to monitor a difficult-to-tune, slow-responding temperature loop that was taking days to tune by hand. Even though it was understood that strong PD control was the proper approach to tuning this loop, the operator could not find the right combination of P and D. Over the course of just several hours (not days), Adapt Tune made several minor recommendations on the P term and several suggested adjustments for the D term to bring the loop under increasingly better control. While in Auto mode, the setpoint was stepped up and down at half-hour intervals to test the response of the new tuning recommendations. The steps were within a healthy operating range for the process.
Don't Deny the D. If properly used, derivative control can enhance your controller response for integrating processes and particularly slow loops. Use it with confidence.
Here's How to Learn More about Process Control
Call for pricing, additional information, or a FREE CONSULTATION on INTUNE with the Adaptive Tuning feature—440-443-3900. Let's explore how INTUNE can help you optimize your tuning parameters while drastically reducing your engineering time.
Free Tuning Tips—Newly Updated!
Request a free copy of PID Loop Tuning Tips Pocket Guide. Click here for request form. Training Class Schedule for Beginning of 2010
We look forward to hearing from you about your PID loop tuning applications. Our goal is to make your job easier. Have a Great Day and Stay Tuned.
|